Agni Junction Fire Services > Conventional Fire Alarm System > Heat Detector Apollo

Heat Detector Apollo

Heat Detector Apollo

 
The Series 65A Heat Detector monitors temperature by using a dual thermistor network which provides a voltage output proportional to the external air temperature.There are nine heat detectors in the Series 65A range designed to suit a wide variety of operating conditions.

can be used for applications where smoke detectors are unsuitable ideal enviroments that are dirty or smoky under normal conditions wide operating voltage flashing LED and magnet operated test switch option.
 

TECHNICAL SPECIFICATIONS
Detector Type Heat Rate – of-Rise/ Fixed Temperature
Working Voltage 9 -33 V DC
Maximum Alarm Current 17mA at 9V, 52mA at 24V
Surge Current 0mA
Supervisory Current 40-50uA at 9V,45uA at 24V
Heat Element ordinary(135*F/57*C)
Ordinary(170*F/77*C)
Intermediate(200*F/93*C)
Compatibility Indentifier 55000-138 to 146
Test method Magnet or hair Dryer
Installation Temperature Minimun 32*F(0*C)
Maximun at least 20*F
(11*C)below rating